Product series • Elsewedy Electric

Elsewedy Medium Voltage Copper Cables XLPE 12/20 kV and 18/30 kV: Sizes and Current Ratings

Elsewedy medium voltage three-core cable

3B Industrial supplies Elsewedy Electric medium voltage cables for factory substations and transformer feeders. This page lists the three-core copper XLPE/PVC sizes on our list for 12/20 kV and 18/30 kV systems, unarmoured and armoured.

Per the Elsewedy catalogue, the cable has a stranded circular compacted copper conductor with a semi-conducting conductor screen, XLPE insulation, a semi-conducting insulation screen and a copper tape or wire metallic screen; the cores are assembled with fillers and PVC sheathed, to IEC 60502, for direct burial or installation on trays or in ducts. Armoured sizes are listed once with steel tape (STA) and once with steel wire (SWA). Codes and values are copied from the catalogue (approximate).

How to choose

  1. System voltage: 12/20 kV for 20 kV networks, 18/30 kV for higher voltages. Check the network voltage with the utility.
  2. Size: pick the size whose current rating covers the transformer or load current for the laying method.
  3. Armour: armoured (STA or SWA) for direct burial where the cable can be damaged.
  4. Send us: voltage, size, armour and length in meters, plus your project specification if you have one.

Can't find your code? Send the part number or a photo of the old part.

Part numbers we supply (48)

Part numberSize and constructionCurrent rating, diameter, weight (catalogue)
CX4-T103-U14 3×50 mm² Cu/XLPE/PVC 12/20 kV 234 A in ground, 229 A in air, Ø 51.3 mm, 3130 kg/km
CX4-T103-G14 3×50 mm² Cu/XLPE/STA/PVC 12/20 kV, steel tape armoured 223 A in ground, 220 A in air, Ø 56.1 mm, 4335 kg/km
CX4-T103-W14 3×50 mm² Cu/XLPE/SWA/PVC 12/20 kV, steel wire armoured 225 A in ground, 223 A in air, Ø 59.3 mm, 6010 kg/km
CX5-T103-U14 3×50 mm² Cu/XLPE/PVC 18/30 kV 236 A in ground, 239 A in air, Ø 62.5 mm, 4055 kg/km
CX5-T103-G14 3×50 mm² Cu/XLPE/STA/PVC 18/30 kV, steel tape armoured 223 A in ground, 224 A in air, Ø 67.5 mm, 5550 kg/km
CX5-T103-W14 3×50 mm² Cu/XLPE/SWA/PVC 18/30 kV, steel wire armoured 225 A in ground, 227 A in air, Ø 72.6 mm, 8370 kg/km
CX4-T103-U15 3×70 mm² Cu/XLPE/PVC 12/20 kV 287 A in ground, 285 A in air, Ø 55.6 mm, 3940 kg/km
CX4-T103-G15 3×70 mm² Cu/XLPE/STA/PVC 12/20 kV, steel tape armoured 274 A in ground, 274 A in air, Ø 60.4 mm, 5245 kg/km
CX4-T103-W15 3×70 mm² Cu/XLPE/SWA/PVC 12/20 kV, steel wire armoured 275 A in ground, 277 A in air, Ø 63.6 mm, 7060 kg/km
CX5-T103-U15 3×70 mm² Cu/XLPE/PVC 18/30 kV 287 A in ground, 292 A in air, Ø 66.8 mm, 4930 kg/km
CX5-T103-G15 3×70 mm² Cu/XLPE/STA/PVC 18/30 kV, steel tape armoured 273 A in ground, 277 A in air, Ø 72 mm, 6560 kg/km
CX5-T103-W15 3×70 mm² Cu/XLPE/SWA/PVC 18/30 kV, steel wire armoured 275 A in ground, 281 A in air, Ø 77.1 mm, 9580 kg/km
CX4-T103-U16 3×95 mm² Cu/XLPE/PVC 12/20 kV 343 A in ground, 346 A in air, Ø 58.4 mm, 4795 kg/km
CX4-T103-G16 3×95 mm² Cu/XLPE/STA/PVC 12/20 kV, steel tape armoured 325 A in ground, 328 A in air, Ø 63.4 mm, 6190 kg/km
CX4-T103-W16 3×95 mm² Cu/XLPE/SWA/PVC 12/20 kV, steel wire armoured 326 A in ground, 331 A in air, Ø 66.6 mm, 8090 kg/km
CX5-T103-U16 3×95 mm² Cu/XLPE/PVC 18/30 kV 344 A in ground, 353 A in air, Ø 69.6 mm, 5825 kg/km
CX5-T103-G16 3×95 mm² Cu/XLPE/STA/PVC 18/30 kV, steel tape armoured 325 A in ground, 333 A in air, Ø 74.8 mm, 7520 kg/km
CX5-T103-W16 3×95 mm² Cu/XLPE/SWA/PVC 18/30 kV, steel wire armoured 326 A in ground, 336 A in air, Ø 80.1 mm, 10735 kg/km
CX4-T103-U17 3×120 mm² Cu/XLPE/PVC 12/20 kV 391 A in ground, 398 A in air, Ø 61.6 mm, 5655 kg/km
CX4-T103-G17 3×120 mm² Cu/XLPE/STA/PVC 12/20 kV, steel tape armoured 368 A in ground, 374 A in air, Ø 66.8 mm, 7165 kg/km
CX4-T103-W17 3×120 mm² Cu/XLPE/SWA/PVC 12/20 kV, steel wire armoured 370 A in ground, 380 A in air, Ø 71.9 mm, 9995 kg/km
CX5-T103-U17 3×120 mm² Cu/XLPE/PVC 18/30 kV 391 A in ground, 406 A in air, Ø 72.8 mm, 6735 kg/km
CX5-T103-G17 3×120 mm² Cu/XLPE/STA/PVC 18/30 kV, steel tape armoured 369 A in ground, 381 A in air, Ø 79.6 mm, 9320 kg/km
CX5-T103-W17 3×120 mm² Cu/XLPE/SWA/PVC 18/30 kV, steel wire armoured 369 A in ground, 383 A in air, Ø 83.3 mm, 11810 kg/km
CX4-T103-U18 3×150 mm² Cu/XLPE/PVC 12/20 kV 439 A in ground, 453 A in air, Ø 64.8 mm, 6580 kg/km
CX4-T103-G18 3×150 mm² Cu/XLPE/STA/PVC 12/20 kV, steel tape armoured 413 A in ground, 424 A in air, Ø 69.8 mm, 8125 kg/km
CX4-T103-W18 3×150 mm² Cu/XLPE/SWA/PVC 12/20 kV, steel wire armoured 413 A in ground, 429 A in air, Ø 75.1 mm, 11080 kg/km
CX5-T103-U18 3×150 mm² Cu/XLPE/PVC 18/30 kV 439 A in ground, 461 A in air, Ø 76 mm, 7705 kg/km
CX5-T103-G18 3×150 mm² Cu/XLPE/STA/PVC 18/30 kV, steel tape armoured 414 A in ground, 431 A in air, Ø 82.6 mm, 10360 kg/km
CX5-T103-W18 3×150 mm² Cu/XLPE/SWA/PVC 18/30 kV, steel wire armoured 412 A in ground, 432 A in air, Ø 86.5 mm, 13010 kg/km
CX4-T103-U19 3×185 mm² Cu/XLPE/PVC 12/20 kV 496 A in ground, 518 A in air, Ø 68.9 mm, 7870 kg/km
CX4-T103-G19 3×185 mm² Cu/XLPE/STA/PVC 12/20 kV, steel tape armoured 464 A in ground, 481 A in air, Ø 74.1 mm, 9545 kg/km
CX4-T103-W19 3×185 mm² Cu/XLPE/SWA/PVC 12/20 kV, steel wire armoured 464 A in ground, 486 A in air, Ø 79.2 mm, 12670 kg/km
CX5-T103-U19 3×185 mm² Cu/XLPE/PVC 18/30 kV 497 A in ground, 527 A in air, Ø 79.9 mm, 9025 kg/km
CX5-T103-G19 3×185 mm² Cu/XLPE/STA/PVC 18/30 kV, steel tape armoured 465 A in ground, 489 A in air, Ø 86.7 mm, 11850 kg/km
CX5-T103-W19 3×185 mm² Cu/XLPE/SWA/PVC 18/30 kV, steel wire armoured 462 A in ground, 489 A in air, Ø 90.6 mm, 14665 kg/km
CX4-T103-U20 3×240 mm² Cu/XLPE/PVC 12/20 kV 576 A in ground, 613 A in air, Ø 74.3 mm, 9760 kg/km
CX4-T103-G20 3×240 mm² Cu/XLPE/STA/PVC 12/20 kV, steel tape armoured 537 A in ground, 565 A in air, Ø 81.1 mm, 12400 kg/km
CX4-T103-W20 3×240 mm² Cu/XLPE/SWA/PVC 12/20 kV, steel wire armoured 532 A in ground, 565 A in air, Ø 84.8 mm, 14980 kg/km
CX5-T103-U20 3×240 mm² Cu/XLPE/PVC 18/30 kV 577 A in ground, 621 A in air, Ø 85.5 mm, 11035 kg/km
CX5-T103-G20 3×240 mm² Cu/XLPE/STA/PVC 18/30 kV, steel tape armoured 536 A in ground, 570 A in air, Ø 92.5 mm, 14100 kg/km
CX5-T103-W20 3×240 mm² Cu/XLPE/SWA/PVC 18/30 kV, steel wire armoured 529 A in ground, 567 A in air, Ø 96.4 mm, 17115 kg/km
CX4-T103-U30 3×300 mm² Cu/XLPE/PVC 12/20 kV 657 A in ground, 716 A in air, Ø 80.3 mm, 11755 kg/km
CX4-T103-G30 3×300 mm² Cu/XLPE/STA/PVC 12/20 kV, steel tape armoured 602 A in ground, 643 A in air, Ø 86.9 mm, 14560 kg/km
CX4-T103-W30 3×300 mm² Cu/XLPE/SWA/PVC 12/20 kV, steel wire armoured 593 A in ground, 639 A in air, Ø 90.8 mm, 17360 kg/km
CX5-T103-U30 3×300 mm² Cu/XLPE/PVC 18/30 kV 657 A in ground, 722 A in air, Ø 91.5 mm, 13120 kg/km
CX5-T103-G30 3×300 mm² Cu/XLPE/STA/PVC 18/30 kV, steel tape armoured 602 A in ground, 647 A in air, Ø 98.5 mm, 16395 kg/km
CX5-T103-W30 3×300 mm² Cu/XLPE/SWA/PVC 18/30 kV, steel wire armoured 591 A in ground, 641 A in air, Ø 102.2 mm, 19540 kg/km